INTERTURN INSULATION TESTER

Download PDF

MODEL : PE 101

Norway

Features: • Ideal for checking of Inter turn Insulation of chokes, coils, transformers, motors etc.
• Checks voltage withstanding capacity between two turns at five times the rated voltage at five times the rated frequency.
• Capacity 500 VA - Higher capacity on request
• Current limit setting facility
• Output short-circuit protected
• Latest PWM technique for highly stable, distortion less sine wave output

TECHNICAL SPECIFICATIONS

Power Input : 230 V AC +/- 10%, 50 Hz
Output Voltage : 800 to 1200 V AC adjustable read of DigitalVolt Meter.
Output Frequency : 240 Hz to 260 Hz adjustable read on Digital Frequency meter
Output Current : 0.5 A at 1000 V AC/500 VA capacity read on Digital current meter
Current Limit : Adjustable from 0.200 to 0.500 A for safe Operation
Facilities :
1 > Output Over Load indication by LED
2 > Input Under Voltage by LED
3 > Input Over voltage by LED
4 > output Short - Circuit Protected
5 > Soft start for Output
6 > High Voltage Control secondary switch

DIGITAL VOLT METER Display : 3 ½ digit 0.5"ht. red LED
Input : 0 - 230 V AC
Indication : 0 - 1200 V AC
Resolution : 1 V AC Accuracy : 0.6% +/- 1 count
DIGITAL CURRENT METERM Display : 3 ½ digit 0.5"ht.red LED
Input from CT internal
Indication 0 - 1.000 A AC
Resolution 0.001 A AC
Accuracy 0.6% +/- 1 count
DIGITAL FREQUENCY METER Display : 4 digit 0.5"ht. red LED
Input : 100 - 230 V AC
Range : 10.0 - 400.0 Hz
Resolution : 0.1 Hz
Accuracy : 0.1% +/- 1 count

Download PDF
1 2 3 4 5 6 7 8 9 10 11 12 13